MV and HV Cable Termination to Equipment and Joints

MV and HV Cable Termination to Equipment and Joints . Proper cable termination is a crucial aspect of ensuring electrical reliability and safety, especially when dealing with medium-voltage (MV) and high-voltage (HV) systems. This guide explores everything you need to know about MV and HV cable termination to equipment and joints, emphasizing best practices and efficient methods.

MV and HV Cable Termination to Equipment and Joints
MV and HV Cable Termination to Equipment and Joints

Read More : Cables Feeder Protection

Understanding MV and HV Cables

Definitions and Key Features

MV cables typically handle voltages between 1 kV and 35 kV, while HV cables are used for voltages above 35 kV. Both are engineered to withstand significant electrical stress and require precise termination to prevent power disruptions or failures.

  • MV Cables: Used in industrial applications, power distribution networks, and utility systems.
  • HV Cables: Primarily used in power transmission to deliver electricity over long distances.

Key features include durable insulation, shielding to manage electric fields, and robust outer sheaths.

General Problems and Factors for Termination

Terminations to indoor switchgears, electric motors, power transformers, instrument transformers and other electrical MV and HV (MV: Medium Voltage; 1 kV < V < 60 kVHV: High Voltage: V ≥ 60 kV) equipment issues arising for multiple terminations design, namely for switchgears, and a straight coordination with manufacturer is required.

MV-HV-Cable-Termination-to-Equipment
MV-HV-Cable-Termination-to-Equipment

Read More : Types of Electrical Wires and Cables

The factors to be considered at the time of electrical machine termination are:

  • Bus and supporting structures
  • Circuit breaker insulation structure
  • PD (partial discharge) analysis
  • Insulation material (oil, SF6 or vacuum)
  • Wedging system condition
  • Cooling gas type
  • Points where a grounded component is located close to a high voltage conductor

Termination for Transition of Underground Cables to Overhead Lines

Terminations for transition of underground cables to overhead lines ( known as OH/OG ) are usually constructed for distribution networks with rated voltages up to 36 kV, for the connection of the distribution system at indoors or outdoors pre-assembled switchgears and also to avoid that overhead lines go through urban areas.

OH/OG are suitable for oil-paper and XLPE (Cross linked polyethylene) insulated cables (single core or 3-core) and are installed outdoors in a metallic structure anchored to the overhead line pole (wood, concrete or metal).

Metallic structures of OH/OG must be grounded.

Read More : What Are the Types of Control and Communication Cables?

Figure 1 – OH/OG cable termination
OH/OG cable termination

The height of the OH/OG metallic structure must be in accordance with the minimum insulation safety distance to ground defined by standards.

The cables shall be erected on the side of the pole away from oncoming traffic and they shall not be bent tighter than the manufacturer’s specified minimum internal bending radius, both during installation and after it has been set in position, what may require taller poles to ensure the minimum bending radius of the cable is not compromised. OH/OG shall be animal proofing.

Read More : Cable and Wire Tester Circuit Diagram

Elbow Terminations

Connection of cables to equipment (transformers, motors or pre-assembled switchgears) terminals mostly uses cable terminations.

However particular conditions of the electrical installation or the equipment terminals may require that cable connection to the bushings shall be sealed.

For that purpose elbow terminations

Elbow termination
Elbow termination

A particular application of elbow terminations is cable connection to bushings of Ring Main Units (RMU).

RMU is a compact self-contained and totally insulated switchgear (SF6), normally used in secondary distribution networks.

The equipment is designed for internal arc withstand, has maintenance free live parts and can be easily extended at site.

Switching function and protection functions are achieved by switch-disconnetors associated to fuses or circuit breakers.

Elbow terminations are also used when more than one cable is required to be connected to the same bushing of equipment, and it can be seen an example of an elbow termination for this situation.

Read More : Proper Size of Wire and Cable in Metric and Imperial Systems

Elbow-termination-for-more-than-one-cable
Elbow-termination-for-more-than-one-cable

Elastimold Cable Joints and Terminations

Elastimold is a very common trade mark of equipments and accessories for cable splicing and termination, for rated voltages up to 36 kV.

Elastimold cable terminations are available in single piece or modular designs, and models are suitable for transition from underground cable to bare overhead conductors, live-front equipment and elbow connections, both for indoor and outdoor applications.

They are suitable for use in oil, SF6 and air insulated high voltage switchgear, transformers, motors and capacitors.

Designs use advanced silicone rubber insulating materials to provide necessary creep, strike, weather sealing and contamination resistance, assuring proper performance in the most severe conditions.

Units are compact and lightweight, allowing installation in restricted spaces and free-hanging applications.

Read More : How Many Pairs Are There in a Twisted Pair Cable?

Elastimold devices are also ATEX (derives from the French title of the 94/9/EC (European Comission) directive: “Appareils destinés à être utilisés enATmosphères Explosibles” ( Equipments to be installed in explosive atmospheres ) certified HV bushings for use within oil or air insulated switchgear and transformers installed in hazardous areas (potentially explosive atmospheres) including the oil, gas and petrochemical industries.

Equipment is manufactured according to IEC, ANSI/IEEE and CENELEC  (IEC: International Electrical Commission. ANSI: American National Standards Institute. IEEE: Institute of Electrical and Electronic Engineers. CENELEC: European Commitee for Electrotechnical Standardization) standards.

Elastimold presents some special devices for particular applications:

Separable elbow connectors and their related accessories are load break connectors that provide a convenient method to connect/disconnect cable and equipment on power distribution systems.

Load break elbows include provisions for energized operation using standard hot stick tools, allowing load make/break operation and a visible disconnect.

Components can be isolated with insulated caps, plugs and parking bushings.

Metal Oxide Varistor (MOV) surge arresters are fully shielded, fully-submersible are constructed for overvoltage protection and 200 A separable connector interfaces for attachment to other Elastimold accessories.

Read More : Why Is the Cable Outer Sheath Black in Color?

Elastimold arresters provide high voltage lightning and switching surge protection of transformers, cable, equipment and other components typically located on underground power distribution systems.

Proper placement, voltage selection and coordination with riser pole arresters minimize damaging surge voltages by improving protective margins.

Typical applications include installing an arrester at the end of a radial system or at both ends of an open point on a loop system.

Additional arresters can be added at strategic locations upstream from the end point for optimum protection.

Fused elbows combine replaceable current-limiting fuses for OH/OG cable termination current protection and 200 A separable connector interfaces for attachment to other Elastimold accessories.

Another trade mark commonly used for cable splicing and termination equipment is Raychem.

Read More : Why Underwater Cables Are So Expensive: The True Cost of Global Connectivity

Terminations to GIS

When the space available for the installation of the substation is short or when the environmental conditions are extremely severe the usual solution is to install a GIS (Gas Insulated Substation).

This kind of equipment is a compact multi-component assembly, enclosed in a ground metallic housing where bus bars, circuit breakers, isolators and instrument transformers are installed , having as primary insulation medium a compressed gas – sulfur hexafluoride (SF6) – that assure the phase to ground insulation.

GIS are usually installed indoors, but models for outdoors installation also exist.

GIS are provided with cable termination enclosures where cable terminations will be installed.

Both enclosures and cable terminations are required in IEC Standard 60859 to meet specified dimension requirements in order to be interchangeable.

Cable terminations for GIS are suitable for gas, oil-paper and XLPE cable insulated and basically they have the same components that cable joints previously discussed.

Read More : Why Do Cables Need Derating in Hot Environments?

Features of GIS Cable termination

Main features of GIS cable terminations are:

  • Cable lug
  • Box body (aluminium alloy or similar).
  • Reliable support insulator – High grade, non-tracking, epoxy insulators provide excellent mechanical and electrical characteristics. The insulators are compatible with SF6 gas by-products, ensuring long life of the termination. Design of the insulators also allows for an optional cable shield break.
  • Filling compound (transformer oil, polybutene oil or similar).
  • Stress control cone with bundle tape.
  • Rigid cable support – The connector is locked in position by a threaded hood at the top of the support insulator. Electrical connection between the GIS and termination should not be subjected to the mechanical forces from the cable.
  • Positive sealing system – A double “O” ring sealing system is used to seal between the termination oil compartment and the GIS SF6 compartment. Fully retained gaskets are compressed to seal the interior of the termination from the atmosphere.
  • Earthing clamp.

a scheme of GIS cable termination; some models on the market do not require oil use and so no oil housing is required.

GIS-cable-termination-scheme
GIS-cable-termination-scheme

Read More : What Are Submarine Cables?

Sealing system must be designed to prevent oil or gas from leaking into GIS.

A mating connection piece, which has to be fitted to the cable end, shall be made available by the GIS supplier.

Facilities to safely isolate a feeder cable and to connect a high-voltage test cable to GIS or the cable shall be provided.

Proper tools and accessories are required for termination for GIS installation:

  • Panduit pliers – for installation of bundle tape around stress cone.
  • Circlip pliers – for installation of top fitting.
  • Adapter flange.
  • Top fitting removal kit.
  • Re-assembly kit
  • Earthing kit.
  • Screen connection.

Safety Precautions

Safety is paramount when dealing with high-voltage systems. Key measures include:

  • Wearing appropriate personal protective equipment (PPE).
  • Adhering to industry standards like IEC 60502 and IEEE 48.
  • De-energizing cables before starting any work.
  • Conducting a risk assessment to identify potential hazards.

Read More : Conduit Systems For Electrical Wires And Cables

Benefits of Proper Termination

1. Efficiency : Correctly terminated cables ensure minimal energy loss and optimal performance.

2. Longevity : Proper installation prevents premature wear and tear, extending the cable’s lifespan.

3. Reduced Downtime : Reliable terminations reduce the likelihood of faults, enhancing system uptime.

Troubleshooting Common Issues

1. Loose Connections : Loose connections can cause overheating. Re-torque connections to the recommended levels.

2. Overheating : Overheating might indicate poor contact or incorrect materials. Inspect and replace faulty components as needed.

3. Environmental Damage : Weather or chemical exposure can degrade materials. Use weatherproof enclosures for added protection.

Read More : Clamper Circuit – Types, Working, and Applications Explained

FAQs

1. What is cable termination?

Cable termination refers to the process of connecting cable ends to equipment or other cables using specialized components and tools.

2. Why is proper cable termination important?

It ensures electrical reliability, safety, and efficiency by preventing faults and maintaining optimal performance.

3. What are the common types of MV and HV cable terminations?

Heat shrink, cold shrink, and pre-molded terminations are widely used.