How to Measure Earth Loop Resistance Using Ammeter and Voltmeter: A Step-by-Step Guide?

Measure Earth Loop Resistance Using Ammeter and Voltmeter

How to Measure Earth Loop Resistance Using Ammeter and Voltmeter? . Earth loop resistance is a critical parameter in ensuring electrical safety and preventing hazards in electrical systems. Properly measuring this resistance helps verify the integrity of grounding systems and identifies potential issues that may lead to equipment failure or unsafe conditions. Among the many methods available, using an ammeter and voltmeter offers an effective approach for accurate measurements.

This article provides a detailed guide on how to measure earth loop resistance using ammeter and voltmeter, the tools required, the step-by-step process, and tips for ensuring accurate results.

Measure Earth Loop Resistance Using Ammeter and Voltmeter
Measure Earth Loop Resistance Using Ammeter and Voltmeter

Read More : What is the Current in Ammeter Connected in Parallel?

How to Measure Earth Loop Impedance Using Ammeter and Voltmeter?

Purpose of measuring earth loop resistance is essentially to determine the resistance of the path through which current flows towards the earth in the event of a short circuit, or to find the resistance of the earth continuity conductor. This is done so that the circuit protective device, such as a circuit breaker or fuse, can act immediately and decisively in the event of a short circuit.

It is crucial to note that as the earth loop impedance decreases, the value of fault current increases, causing the circuit breaker or fuse to act more promptly. If the earth loop resistance is high, the circuit breaker or fuse may not open quickly during a fault due to the lower fault current flow. This could lead to hazardous situations. Therefore, it is essential to measure the earth loop resistance value using this test so that the operation of the circuit breaker or fuse in the event of a fault can be ensured.

Read More : What Is the Difference Between Analog and Digital Multimeter?

This test can be conducted using an earth loop resistance tester, megger, digital ground/earth resistance tester or with the use of a voltmeter and ammeter.

In this tutorial, we will be using an voltmeter and ammeter to measure and calculate the earth loop resistance for specific circuit(s). It is important to ensure that the value of the current flowing through the earth loop is not more than 1.5 times the current rating of the circuit.

Before conducting this test, it is necessary to perform the insulation resistance test between the neutral and earth to ensure that the neutral is properly insulated from the earth.

Tools and Equipment Required for Measure Earth Loop Resistance

To measure earth loop resistance accurately, gather the following tools and equipment:

Essential Tools:

  1. Ammeter: To measure current flow in the circuit.
  2. Voltmeter: To measure voltage across the earth loop.
  3. Test Leads: For connections between devices and the system.
  4. Earth Electrode: A metal rod or conductive plate driven into the ground.

Read More : Short Circuit and Open Circuit Test of Transformer

Additional Items:

  • Insulated gloves for safety.
  • Multimeter (optional for additional verification).
  • A circuit diagram of the setup.

Measuring Earth Loop Resistance using Ammeter and Voltmeter

To measure the earth loop resistance, one cable of the circuit is used as the return path (utilized as the return path for fault current) and connected to the farthest point of the earth continuity conductor. The procedure for measuring earth loop impedance using an ammeter and voltmeter is demonstrated in the following fig.

Measuring-Earth-Loop-Resistance-using-Ammeter-and-Voltmeter
Measuring-Earth-Loop-Resistance-using-Ammeter-and-Voltmeter

Read More : Difference Between Electric Current and Electric Charge

The maximum voltage from the transformer secondary windings is 40 volts. The testing leads coming out of the secondary side of the transformer are connected to the termination point of the cable and bonded to the ground rod / earth electrode (as shown in the diagram).

This completes the circuit, and the current flows through the continuity conductor. The value of this current is adjusted to 1.5 times the circuit current rating through a rheostat so that the current does not exceed 25 amperes.

For example, if the circuit current rating is 10 amperes, the transformer supplies 15 amperes to the circuit. Afterward, the voltmeter and ammeter readings are noted, and the total earth loop resistance value is determined using Ohm’s law formula.

Total Loop Resistance = Voltage ÷ Current

= Reading of Voltmeter ÷ Reading of Ammeter

RL = V ÷ I

Since the resistance of the wiring cable used as the return path is included in the total value of this resistance, the resistance of the wiring cable should be subtracted from the total resistance value to determine the actual resistance value of the earth continuity conductor. The resistance of a specific cable and wire, determined by its length and size, can be found by using the resistance tables for the cable’s conductors.

Earth Loop Resistance = Total Loop Resistance − Resistance of Wiring Cable 

The value of earth loop resistance should not be more than one ohm (1-Ω) in the case of a copper conductor and not more than half an ohm (0.5Ω) in the case of a steel conduit.

Read More : Design and Installation of EHV/EHV and EHV/HV Substations

Why Measure Earth Loop Resistance?

1. Ensuring Electrical Safety : Low resistance ensures a quick response from circuit breakers or fuses during faults, reducing the risk of electrical shocks or fires.

2. Compliance with Standards : Regulatory bodies like IEEE and IEC mandate specific resistance levels for grounding systems.

3. Preventing Equipment Damage : Proper grounding reduces the likelihood of voltage surges damaging sensitive equipment.

Applications of Measuring Earth Loop Resistance

1. Residential and Commercial Buildings : Verifies grounding systems for circuit breakers and fuses.

2. Industrial Settings : Ensures safety for heavy machinery and sensitive equipment.

3. Power Distribution Networks : Evaluates grounding performance in substations and power plants.

Read More : What is the Difference Between Analog and Digital Circuit?

FAQs

1. Why is earth loop resistance important?

It ensures the effectiveness of grounding systems, protects equipment, and enhances safety by reducing the risk of electrical hazards.

2. What is an acceptable earth loop resistance value?

Generally, resistance should be less than 1 ohm for most installations, though specific requirements may vary.

3. Can I use a multimeter instead of an ammeter and voltmeter?

Yes, a multimeter can serve both functions, but ensure it is rated for the expected voltage and current ranges.

4. How often should earth loop resistance be tested?

Testing is recommended annually or whenever significant changes occur in the electrical system.

5. What is the difference between earth resistance and earth loop resistance?

Earth resistance measures the grounding electrode’s connection to the ground, while earth loop resistance considers the complete loop, including live and neutral paths.

6. Is it possible to measure earth loop resistance without disconnecting power?

Yes, using a clamp-on meter allows non-intrusive measurements, but it may not be as precise as traditional methods.