How to Check Earthing and Measure Ground Resistance using a Multimeter?
Measuring ground resistance using a multimeter is generally not as accurate as using specialized ground resistance testers, but it can provide a rough estimate. Most multimeters are designed for measuring voltage, current, and resistance in low-power circuits. Here’s a basic guide on how to measure ground resistance and test the grounding system’s proper functionality using a multimeter:
Good to Know:
- According to NEC 250.56, the maximum grounding resistance is 25 ohms, and 50 ohms for sensitive applications. An additional ground rod needs to be installed if the ground resistance exceeds 50 ohms.
- According to IEC/BS EN 62561-2:2012, good earth resistance is 5 – 10 ohms.
- Recommended grounding resistance per IEEE and NFPA standards is typically < 5 ohms, also applicable to telecommunications.
Testing the grounding system using a multimeter is an essential step to ensure the safety and effectiveness of electrical installations. Here’s a general guide on how to test the grounding system using a multimeter:
Measuring the Grounding Resistor Using Multimeter
Materials Needed:
- Multimeter: Ensure that it’s capable of measuring resistance (ohms – Ω).
- Grounding Rod or Electrode: The grounding system typically involves a ground rod or electrode, which is a metal rod buried in the ground.
Steps to Measure the Grounding Resistance:
1. Set Up the Multimeter:
- Turn off power:
- Before connecting the multimeter, ensure that power to the system you are testing is disconnected to ensure safety.
- Select the ohm (Ω) setting: Set your multimeter to the ohm setting. This is typically indicated by the symbol “Ω.” Choose an appropriate range for the expected resistance values in the grounding system.
2. Check the Multimeter:
- Before connecting the multimeter to the grounding system, ensure that the multimeter is functioning properly by touching the probes together. The multimeter should show a very low resistance, as the probes are shorted.
- Identify the grounding system or electrode you want to measure. Clean the connection points to ensure good electrical contact.
3. Connect the Probes:
- Connect the black (COM – Negative) lead of the multimeter to a known good ground, such as a metal water pipe or a designated ground rod.
- Connect the Red (Positive) lead of the multimeter to the point in the grounding system you want to measure. This could be a ground rod, grounding electrode, other grounding connection like grounding port in an outlet. grounding terminal or metallic part (body) or chassis of a machine.
4. Measure Resistance:
- Observe the reading and record the resistance value displayed on the multimeter. The multimeter should display the resistance between the grounding rod and the known reference ground. A low resistance (ideally close to 0 ohms) indicates a good grounding connection.
5. Compare the Results:
Compare the measured resistance with any applicable standards, local area codes and guidelines. Ground resistance values can vary depending on the specific requirements of the system.
- Low resistance: If you get a low resistance reading, it means that there is a good connection between the grounding rod and the known ground. This is desirable for a proper grounding system.
- High resistance: If you get a high resistance reading, it indicates a poor grounding connection. This could be due to corrosion, loose connections, or other issues that need to be addressed.
Testing the Grounding & Earthing System using a Multimeter
A digital or analog multimeter can be used to test and check if the earthing or grounding system is working properly. As it is a handy and DIY quick fix method, however, it’s important to note that this method may not be as effective. For higher accuracy, consider using a digital earth-ground resistance tester or a megger. If you’re still unsure, it’s advisable to contact a licensed electrician to perform the job in compliance with local area codes and regulations.
To verify the proper functioning of the grounding system using multimeter, follow these steps:
Testing the Ground System in 120V Circuit
Materials Needed:
- A Digital or analog Multimeter
- 120V or 240V / 230V Outlet / Receptacle / Socket
Steps to Test the Grounding System:
1. Set Up the Multimeter:
- Select the ACV Mode setting: Set your multimeter to the ACV (alternating current and voltage) setting. This is typically indicated by the symbol “~.” above the V. In analog multimeter, choose an appropriate range (250V in multimeter for 120V, 230V/240V testing circuit) for the expected resistance values in the grounding system.
2. Check the Multimeter:
- Before connecting the multimeter to the grounding system, ensure that the multimeter is functioning properly by touching the probes together while in resistance (ohm – Ω) mode . The multimeter should show a very low resistance or make a beep to show the short circuit, as the probes are shorted.
- Identify the desired outlet you want to make a test for grounding system. Clean the connection points to ensure good electrical contact.
3. Connect the Probes:
- Test 1:
- Connect the Black (COM – Negative) lead of the multimeter to the wider blade (Neutral) of ordinary 120V outlet.
- Connect the Red (+ Positive) lead of the multimeter to the narrow blade (Hot or Line) of the outlet.
- Observe the reading. The meter will display near to 120V. For example, Note the reading of 120V.
- Test 2:
- Connect the Red (+ Positive) lead of the multimeter to the narrow blade (Hot or Line) of the 120V outlet.
- Connect the Black (COM – Negative) lead of the multimeter to the ground port of the outlet.
- Observe the reading. The meter will display near to 120V. For example, Note the reading of 121V.
- Test 3:
- Connect the Black (COM – Negative) lead of the multimeter to the wider blade of 120V outlet.
- Connect the Red (+ Positive) lead of the multimeter to the ground port of the outlet.
- Observe the reading. The meter will display between 0 to 5V. For example, Note the reading of 0.5V.
Calculate the Leakage Voltage (Must be Less than 2V)
Leakage refers to the voltage moving from the ground/earth terminal to the neutral. If the leakage voltage exceeds 2V, the earthing – grounding system is likely faulty, and it is advisable to contact an electrician to configure it properly.
Based on the tested and recorded readings, calculate the total leakage on the outlet using the following formula:
(VPN + VPG) + VGN
Where:
- V = Voltage between Phase and Neutral
- V = Voltage between Phase and Ground
- V = Voltage between Ground and Neutral
Putting the values,
(121V + 120V) + 0.5V
= 1V + 0.5V = 1.5V
4. Compare the Results:
Compare the measured resistance with any applicable standards, local area codes and guidelines. Ground resistance values can vary depending on the specific requirements of the system. Based on the recorded values from above tests:
Good Grounding System:
- If the reading of tested voltage between Hot (Phase) and Neutral (say 120V) is almost equal to the tested voltage between Hot (Phase) and Ground port (say 121V).
- If the value of leakage voltage is less than 2V (based on calculated value as above).
Faulty Grounding System:
- If the reading of tested voltage between Hot (Phase) and Ground port is more than 1% e.g. 3V for 120V or 5V for 230V/240V.
- If the value of the leakage voltage is more than 2V (based on calculated value as above).
No Grounding System:
- If the reading of tested voltage between Hot (Phase) and Ground port is 0V. It shows there is no grounding system or the ground wire is broken somewhere in the middle.
FAQ
How to test for a ground fault with a multimeter?
After that, connect one probe to the equipment’s metal frame or casing and the other probe to the ground wire or prong of the plug. Check the reading on the multimeter. If it is close to zero, it means there is a ground fault. If it is very high or infinite, it means there is no ground fault
How do you test a ground rod with a multimeter?
Clamp a ground meter around the grounding electrode conductor and turn it on. A reading under 25 ohms generally means the ground rod has a good connection to the earth
How to check short to ground with a multimeter?
To check for a short to ground with a multimeter, I would first set the multimeter to the ohm setting. I would then touch one probe to the ground wire and the other probe to the wire that I think may be shorted to ground. If the multimeter beeps or reads 0 ohms, then there is a short to ground
What is the ohm test for ground?
Ground testing requirements
Both the National Fire Protection Association (NFPA) and IEEE recommend a ground resistance value of 5.0 ohms or less. But, when you dive further into the National Electric Code (NEC), section 250.56 says that you want to make sure the system to ground is 25.0 ohms or less
What is the 3 point test for grounding?
Fall-of-Potential Method or 3-Point Test
In this test, a short probe, referred to as probe Z, is driven into the earth at a distance of ten times (10X) the diagonal length of the grounding system (rod X). A second probe (Y) is placed in-line at a distance from rod X equal to the diagonal length of the grounding system
How to find a grounding fault?
You can use a multimeter to check for continuity between the hot wire and the ground wire of a circuit. If there is continuity, it means there is a direct connection between them, which indicates a ground fault. You can also use a multimeter to measure the resistance between the hot wire and the ground wire